Installed in a way that it is sandwiched between the pipe flanges! Flow measurement is possible!
The "ORT" is a flange-type orifice plate that is installed between pipe flanges to create a differential pressure based on the flow rate of liquids, gases, and steam, allowing for flow measurement using differential pressure gauges and transmitters. The design and construction of the pipe flanges are carried out by the customer, while the orifice plate is designed and manufactured by our company based on orifice calculations in accordance with JIS standards. Additionally, differential pressure gauges and transmitters are available as options. *For more details, please refer to the PDF materials or feel free to contact us.*
Inquire About This Product
basic information
【Specifications】 ■Model: ORT ■Manufacturing Diameter: 50A to 500A ■Measured Fluid: Liquid, Gas, Steam ■Maximum Operating Pressure: According to flange standards ■Installation Method: Wafer (Flange sandwich type) ■Pressure Extraction Method: D, D/2 tap, flange tap ■Orifice Calculation: JIS Z 8762-2:2007 ■Material: SUS304 (standard), SUS316, others ■Connections ・JIS 10K flange (standard) ・JIS 5K, 16K, 20K, 30K flanges ・ANSI flange, JPI flange *For more details, please refer to the PDF document or feel free to contact us.
Price range
Delivery Time
Applications/Examples of results
For more details, please refer to the PDF document or feel free to contact us.
catalog(1)
Download All CatalogsCompany information