RS485 Modbus communication and automatic control equipment for air conditioning
RS485 Modbus RTU - Automatic Control Equipment for Air Conditioning
It is an automatic control device for air conditioning, such as sensors with communication functions, damper actuators, and valves, which can reduce the labor required for wiring work.
This product has general-purpose RS485 Modbus RTU communication functionality. It can connect sensors, damper actuators, valves, etc., to the controller using a two-core twisted pair cable. 【Features】 - Each product has a power line and communication line that allows for simplified wiring work. - For example, the wiring for sensors and damper actuators inside air conditioning units becomes simpler. - Simplifying the wiring reduces the possibility of connection errors during installation. - No additional input/output expansion units are required on the controller side (it can be completed with just one terminal for communication). - Wireless communication for the communication line is also possible, further simplifying wiring work.
Inquire About This Product
basic information
Main Products - Indoor temperature (temperature and humidity) sensor - Indoor CO2 sensor - Duct temperature (temperature and humidity) sensor - Duct CO2 sensor - Room unit - Damper actuator - Control valve (electric ball valve) - Accumulated heat meter
Price information
Please contact us regarding the price.
Delivery Time
※According to the meeting.
Applications/Examples of results
It is an automatic control device for air conditioning equipped with general-purpose RS485 Modbus RTU communication functions, allowing sensors, damper actuators, valves, and other components to be connected to the controller using a 2-wire twisted pair cable.
Detailed information
-
Indoor Temperature Sensor Model: WRF04 Power Supply: DC 24V ±10% Power Consumption: 0.6 VA Measuring Temperature: 0 to 50°C Measurement Accuracy: ±0.5°C or less (at 25°C) Product Weight: 85g
-
Indoor Temperature and Humidity Sensor Model: LCN-FTW04 Power Supply: DC 24V ±10% Power Consumption: 0.6 VA Measuring Temperature: 0 to 50°C Measuring Humidity: 10 to 90% RH Product Weight: 95g
-
Indoor CO2 Sensor Model: WRF04 CO2 Power Supply: DC 24V ±10% Power Consumption: 3VA CO2 Concentration Measurement: 0–2000 ppm Measurement Method: Non-dispersive Infrared Absorption (NDIR) Product Weight: 95g
-
Duct Temperature Sensor Model: AKF10 Power Supply: DC 24V ±10% Power Consumption: 0.7W Measuring Temperature: -20 to +100°C Product Weight: 120g
-
Duct Temperature and Humidity Sensor Model: FTK... Supply Voltage: DC 24V ±10% Power Consumption: 1.8 VA Measuring Temperature: -20 to +80°C Measuring Humidity: 0 to 100% RH Product Weight: 170g
-
Room unit Model: Thanos... Indoor temperature display and temperature setting Indoor humidity display and humidity setting Equipment operation stop Others (depending on settings)
-
Damper Actuator Model: NM24A-MOD Rated Torque 10Nm Model: SM24A-MOD Rated Torque 20Nm Model: GM24A-MOD Rated Torque 40Nm Supply Voltage: DC 24V ±10% / AC 24V ±10% 50/60Hz Operating Time: Approximately 150 seconds / 90° Interface: Modbus RTU (RS485), non-isolated Product Weight: 830–1800g
-
Control Valve Model: NR24A-MOD Diameter: 15A to 50A
Company information
Archback is an independent company that received a business transfer from Landis & Gyr and Siemens Building Technologies. We mainly handle HVAC automatic control systems and central monitoring devices, and we are committed to bridging building management and HVAC automatic control in Europe and Japan.