One unit (module) can control the temperature at four points. Up to 16 temperature control modules can be connected in series. A maximum of 64 points of temperature control is possible.
One unit (module) can control four points. When connecting each module, the power supply and communication lines are internally connected, eliminating the need for separate wiring for power and communication for each module, thus achieving reduced wiring. The inputs are universal inputs compatible with thermocouples, resistance temperature detectors, voltage, and current. The type of input can be specified for each channel, allowing for combinations of different inputs. Additional function modules aside from temperature control are available, including digital input/output modules (for operation mode switching, event output, etc.), communication expansion modules (for communication conversion and data management during module connection), and CT input modules (for heater disconnection alarm CT input and multi-point CT monitoring/overcurrent alarm). Various fieldbus communication converters can be connected, including Ethernet-based networks (MODBUS/TCP, EtherCAT, PROFINET), CC-Link, DeviceNet, PROFIBUS, and MECHATROLINK.
Inquire About This Product
basic information
Temperature Control Module Number of Input Points: 4 points or 2 points Input Types (Universal Input): Thermocouple, Resistance Temperature Detector, DC Voltage, DC Current Sampling Cycle: 0.25 seconds Measurement Accuracy: ±(0.2% of displayed value + 1 digit) Output Relay Contacts, SSR Drive Voltage Pulse, Current, Voltage, SSR (Triac) Output, Open Collector Output Digital Input/Output Module Number of Input Points: 0 or 8 points Input Method: Voltage Contact Input, Sink Method Number of Output Points: 0 or 8 points Output Types: Relay Contact Output, Open Collector Output, Sink Method Current Detector Input Module Number of Input Points: 12 points Communication Expansion Module Number of Modules Connectable: Up to 16 modules of the same function, total number of connectable modules up to 31 Communication Method: RS-485 / RS-422A Maximum Number of Connectable Units: 4 units <Common Specifications> Power Supply Voltage: DC24V Safety Standards: UL: UL61010-1, cUL: CAN/CSA-22.2 NO.61010-1 CE Marking: Low Voltage Directive (LVD): EN61010-1, EMC Directive: EN61326-1 RCM: EN55011
Price range
Delivery Time
Applications/Examples of results
Heater temperature control
Detailed information
-
Compatible with Ethernet-based networks (MODBUS/TCP, EtherCAT, PROFINET). Communication converters for connecting to CC-Link, DeviceNet, PROFIBUS, and MECHATROLINK are also available.
-
Programless connection is possible with Mitsubishi Electric's MELSEC series PLC.
catalog(3)
Download All CatalogsCompany information
Our company, as a service provider in measurement and control, is engaged in the sale of advanced products and research and development to meet the diverse needs of the industrial sector through hardware (various control instruments such as industrial control devices for temperature, pressure, power, etc., communication converters connected to field networks, control devices specially designed for customer equipment and machinery, sensors for high-precision measurements of temperature, pressure, etc.) + software (proposals to customers, engineering, before-service, after-service, support) + peripheral device solutions.