Industry first*! This single unit can perform both phase and non-phase checks.
Charging display function: Determines charging status (ground voltage of 80V or higher) and clip connection failures. Non-contact type: Allows checking of phase rotation and same-phase/different-phase from above insulated wires. Applicable wire size: Wide range from 2mm² to 100mm² (finished outer diameter φ2.8 to 22mm). Can be checked hands-free using the magnet mounted on the back of the main unit. *As of June 2015, according to manufacturer research.
Inquire About This Product
basic information
■Specifications Model Number: M132PL-LV200H Applicable Circuit: Three-phase 3-wire and three-phase 4-wire Applicable Voltage Range: AC 80–600V (sine wave, continuous) Frequency: 50Hz/60Hz Insulation Resistance: AC 2,000V for 1 minute (between clip and case) Leakage Current: Below 100μA during insulation resistance testing Power Indicator: One red LED (auto power off after approximately 5 minutes) Sound Level: Above 50dB (at a distance of 50cm) Battery Used: LR03 (AAA alkaline battery) x 2 Continuous Use: Approximately 15 hours Target Wires: IV, DV, 0W, 2mm² to 100mm² (finished outer diameter φ2.8 to 22mm) Weight: Approximately 190g (including batteries)
Price range
Delivery Time
Applications/Examples of results
*Display of 2 used clips, unused ones are lit up.
Company information