Fire safety control panel
Due to the aging of certain building equipment, we considered updating the fire protection systems. When using the current fire generator capacity calculation software, it was determined that the existing emergency generator was insufficient in capacity, which posed a challenge for us. As a solution, we recalculated using the V-Star (special condor fan), and were able to fit within the capacity of the existing generator. Therefore, we adopted the V-Star starter, eliminating the need to replace the generator.