Remove the corrosive gas occurring in the control room and achieve stable operation.
At the pulp dissolving facility of the paper mill, corrosive gases were generated and flowed into the adjacent machine control room, causing corrosion of the control boards and resulting in frequent emergency stops of the machines. Issues: 1. The machine building, including the dissolving equipment, is maintained at positive pressure, causing the generated corrosive gases to flow into and fill the adjacent control room. 2. Corrosive gases such as sulfur dioxide and hydrogen sulfide are being produced, but the exact composition and concentration of the gases are unknown. 3. Due to the inability to accurately determine the gas composition, effective countermeasures cannot be implemented.
Inquire About This Product
basic information
We proposed to analyze the corrosive gas and implement a corrosion control system tailored to the results. Points: 1. Install corrosion classification coupons (sampling testers for corrosive gas analysis) in the control room to accurately analyze the corrosive gas. 2. Classify based on the analysis results (degree of corrosion of gold, silver, and copper plates) according to the US standard ISAstd. 3. Determine the type and required quantity (number of units) of gas adsorbents based on the classification. 4. Decide on the capacity of fans and other equipment, and assemble the corrosion control system considering the installation space. * To enhance effectiveness, we also suggested that the customer improve the airtightness of the control room.
Price range
Delivery Time
Applications/Examples of results
For more details, please contact us.
catalog(1)
Download All CatalogsCompany information
In today's world, where advanced technological capabilities are required of all Japanese companies, we aim to be a trading company that not only embodies "integrity" and "technology," but also explores our customers' needs and responds to their requests, rather than being just a simple trading company.